Inor IPAQ
Isolated Programmable 2-Wire Transmitter for RTD and T/C
IPAQ is an intelligent 2-wire transmitter for temperature and other measurement applications. IPAQ-HX is the Intrinsic Safe version for use in Exapplications. The Windows based and user friendly software, IPRO 4, is used for transmitter configuration, documentation, monitoring and calibration purposes.
Ordering Information
Type | Part Number | Price |
IPAQ-H,Isolated | 70lPH00001 | 165.00 |
IPAQ-HX, Isolated (FM) | 70lPHX1001 | 195.00 |
IPAQ-L,Isolated | 70lPL00001 | 165.00 |
IPAQ-LX, Isolated (ATEX) | 70lPLX0001 | 195.00 |
IPAQ-LX, Isolated (FM) | 70lPLX1001 | 195.00 |
PC Configuration Kit | 70CFGUS001 | 350.00 |
Lead Time
5 Business Days from Date of Approved Order
IPAQ is an intelligent 2-wire transmitter for temperature and other measurement applications. IPAQ-HX is the Intrinsic Safe version for use in Exapplications. The Windows based and user friendly software, IPRO 4, is used for transmitter configuration, documentation, monitoring and calibration purposes.
Input
RTD's and Resistance
Pt100 (IEC751, a=0.00385) 3-,4-wire connection
-200 to +1000 °C/ -328 to +1832°F
Pt1000 (IEC751, a = 0.00385) 3-, 4-wire connection
-200 to +200 °C/ -328 to +392 °F
PtX 10 £ X £ 1000 (IEC751, a = 0.00385) 3-, 4-wire connection
Ni100 (DIN 43760) 3-, 4-wire connection -60 to +250 °C
Ni1000 (DIN 43760) 3-, 4-wire connection -60 to +150 °C
D100 (Pt 100 acc.to JIS1604, a = 0.003916) 3-, 4-wire connection
-200 to +1000 °C / -328 to +1832 °F
Thermocouples and Voltage T/C Type:
AE, B, E, J, K, L, N, R, S, T, U
Ranges according to user’s manual
Voltage input
-10 to +500 mV
Input impedance >10 MW
Maximum sensor wire resistance 500 W (total loop)
Monitoring
Sensor break monitoring User definable output 3.5 to 21.6 mA
Smart Sense, sensor isolation monitoring
User definable output 3.5 to 21.6 mA
Adjustments
Zero adjustment All inputs Any value within range limits
Minimum spans Pt100, Pt1000, Ni100, Ni1000 10 °C / 18 °F
Potentiometer 10 W
T/C, mV 2 mV
Output
4-20/20-4 mA Temperature Linear Resolution 5 mA
General data
Galvanic Isolation
1500Vac 1 MIN, iPAQ-PLUS 3750 Vac
Typical Accuracy
+/-- 0.1% Span IPAQ plus +/- 0.05%
Intrinsic safety
I PAQ-HX, ATEX II 1 G EEx ia IIC T4, T5, T6
FM Class I, Div. 1, Group A-D, T4
Supply voltage
IPAQ-H 6.5 to 36 VDC 2-wire IPAQ-L 7.5-36 VDC
IPAQ-HX and LX 8.0 to 30 VDC 2-wire